Gas Fire Extinguishing System Installation Requirements

Gas Fire Extinguishing System Installation Requirements

In order for the gas fire extinguishing system to function properly, we must pay attention to the following aspects when installing the equipment.

       The location of the pressure gauge, level gauge, and weighing display device on the fire extinguishing agent storage device should be easy to observe and operate. After the installation of the fire extinguishing agent storage device, the pressure relief device should not be directed toward the operating surface. The safety valve of the low-pressure carbon dioxide gas fire extinguishing system shall be connected to the outside through a dedicated pressure relief pipe. If the installation height of the selector valve exceeds 1.7m, measures shall be taken to facilitate the operation. The direction indicator arrow of the selector valve should point in the direction of flow of the medium. After the fire extinguishing agent delivery pipeline is installed, the strength test and air tightness test shall be carried out and qualified. When the nozzle is installed under the ceiling without a decorative cover, the thread of the pipe end of the connection pipe shall not be exposed from the ceiling; the nozzle with a decorative cover installed under the ceiling shall be close to the ceiling.

       The above is the installation requirements for the gas fire extinguishing system for your reference.